Figure 6-13 - group comm, Table 6-6 - group communication fields, Figure 6-13 – Gasboy Fuel Point PLUS Station User Manual
Page 60: Table 6-6
60
Fuel Point PLUS Station Equipment Manual
Figure 6-13 - Group Comm
1.
In the
FCC to Group
section, in the
Comm. Interface
drop-down, select
TCP/IP
. Once this
option is selected the
TCP/IP Port
field is displayed
2.
In the
FCC to Group
section, in the
TCP/IP Port
field enter the port number (between 3000 and
4000)
3.
In the
Group Communication
section, in the
Group Address
field, enter the RS-485 address of
the group (between 31 and 39)
4.
In the
Group Communication
section, in the
Comm. Interface
drop-down, select
Wireless
5.
Repeat Steps 1-4 for each Group defined while
6.
Click
Submit
Field
Description
FCC to Group
Comm.
Interface
Communication interface between the Station Controller and the group. Usually, the Master Wireless Gateway is
connected to the Station Controller via Ethernet and therefore TCP/IP option should be selected
Note
: Serial communication interfaces are also available for backward compatibility to wired legacy systems.
TCP/IP
Port
Port as defined in Station Controller (between 3000 and 4000)
Group Communication
Table 6-6 - Group Communication Fields