Warning: Do not mix old and new batteries or

battery types. Use only P/N 812539200

(Manufacturer P/N XENO XLP-055F)
6. Replace the lid and secure it with the two Phillips

screws.

7. Verify that the indication LED blinks when the

unit is tilted

8. Insert the µNozzle Reader assembly back into

place, then close the back clamp and secure it

with the two Allen screws.

Note: Discharged Lithium and Lithium Ion

batteries are currently designated to be disposed

of in normal trash. However, users should

contact their municipal waste disposal facility

prior to discarding any used battery in normal

trash.

8. TROUBLESHOOTING

Table 3 provides troubleshooting guidelines intended to assist the technician in solving common issues related to µNR units.

Table 3. µNR Troubleshooting

Symptom

Probable Cause

Corrective Action

LED does not blink

when the unit is tilted

Defective µNR

Replace µNR unit

Drained battery

Replace battery

LED does not blink

twice when attached

to a FuelOpass

µNR was removed during refueling and then

inserted into another vehicle's fuel filler

Resume refueling the first vehicle

before reuse

µNR is disconnected from µNR assembly

Replace µNR unit

Drained battery

Replace battery

Defective FuelOpass

Verify that the FuelOpass is valid

and readable

Reprogram/replace FuelOpass

LED blinks twice but

fueling does not start

FuelOpass is restricted

Verify that the vehicle is allowed

to refuel according to

rules/restrictions

Defective FuelOpass

Verify that the FuelOpass is valid

and readable

Reprogram/replace FuelOpass

LED blinks three

times

µNR is deactivated

Reactivate the unit with Station

Manager Tag, WP/NR-P or

MWGT Site