Troubleshooting – Gasboy Fuel Point PLUS Station User Manual
Page 134
Warning: Do not mix old and new batteries or
battery types. Use only P/N 812539200
(Manufacturer P/N XENO XLP-055F)
6. Replace the lid and secure it with the two Phillips
screws.
7. Verify that the indication LED blinks when the
unit is tilted
8. Insert the µNozzle Reader assembly back into
place, then close the back clamp and secure it
with the two Allen screws.
Note: Discharged Lithium and Lithium Ion
batteries are currently designated to be disposed
of in normal trash. However, users should
contact their municipal waste disposal facility
prior to discarding any used battery in normal
trash.
8. TROUBLESHOOTING
Table 3 provides troubleshooting guidelines intended to assist the technician in solving common issues related to µNR units.
Table 3. µNR Troubleshooting
Symptom
Probable Cause
Corrective Action
LED does not blink
when the unit is tilted
Defective µNR
Replace µNR unit
Drained battery
Replace battery
LED does not blink
twice when attached
to a FuelOpass
µNR was removed during refueling and then
inserted into another vehicle's fuel filler
Resume refueling the first vehicle
before reuse
µNR is disconnected from µNR assembly
Replace µNR unit
Drained battery
Replace battery
Defective FuelOpass
Verify that the FuelOpass is valid
and readable
Reprogram/replace FuelOpass
LED blinks twice but
fueling does not start
FuelOpass is restricted
Verify that the vehicle is allowed
to refuel according to
rules/restrictions
Defective FuelOpass
Verify that the FuelOpass is valid
and readable
Reprogram/replace FuelOpass
LED blinks three
times
µNR is deactivated
Reactivate the unit with Station
Manager Tag, WP/NR-P or
MWGT Site