beautypg.com

Approved location, Installation instructions, Figure 5-1 - approved location – Gasboy Fuel Point PLUS Station User Manual

Page 42

background image

42

Fuel Point PLUS Station Equipment Manual

5.3. Approved Location

Due to safety requirements, the Wireless Gateway outdoor must be installed at non-hazardous area/non-
classified area (see

Figure 5-1

):

Above 18” (0.5 meter) from the Isle floor
At least 18” (0.5 meter) away from the dispenser

18"/0.45m

18"/0.45m

18"/0.45m

Wireless

Gateway

Outdoor

Class I Div 2 Safety Area

Figure 5-1 - Approved Location

5.4. Installation Instructions

1.

Remove the Wireless Gateway front panel

2.

Remove the cable entry knockout plates on the bottom panel:

For Master Wireless Gateway remove two panels (one for LAN and one for Power

cables)

For Wireless Gateway remove one panel for the Power cable

3.

Place the unit vertically with cable entry openings facing down

4.

Secure the unit to a flat surface, inserting four screws in the mounting openings located at the four
corners of the unit (see

Figure 5-2

,

Figure 5-3

5.

Connect power supply:

For units equipped with integrated P/S: Connect AC P/S to the AC terminal
For units without integrated P/S: connect a 12-28 VDC (stabilized),0.5A power supply

to the Power Connector
Use an external AC to DC or DC to DC switching power supply transformer approved
according to the local regulations. In North America use a AC to DC NEC Class 2 power
supply, low voltage and low current maximum 100 VA even under fault conditions. The
power supply can be installed in the office, in the pedestal, in the tanker truck cabin (DC
to DC power supply) or in a separate box