GF-135 Esteem 399 Low NOx Boiler

Chapter 11

OMM-0089_0A

Installation, Operation & Maintenance Manual Start-Up Preparation

11.6 INSPECTION OF CONDENSATE DRAIN ASSEMBLY

Inspect the condensate drain assembly as follow.

Inspecting the Condensate Drain assembly

1. Inspect and ensure the Condensate Drain Assembly is properly installed as shown in

Figure 6-1 of Chapter 6.

2. Remove the plug from the Condensate Drain Assembly and fill with fresh water.

WARNING!

The condensate drain assembly must be filled with water when the

Esteem boiler is in operation. The condensate drain assembly

prevents flue gas emissions from entering the condensate line.

Failure to ensure trap is filled with water could result in severe

personal injury or death.

3. Re-Install the plug into the condensate drain assembly.






















Page 89 of 188