Installation, Operation & Maintenance Manual

Boiler Piping

NOTE

To ensure an adequate flow rate through the Esteem boiler, the

boiler supply and return piping size must be a minimum 1-1/2

inches.

5.13 SYSTEM PIPING - ZONE VALVES

Connect the Esteem boiler to the system piping as shown in Figure 5-6 when zoning with zone valves.

The primary / secondary piping ensures that the boiler loop has sufficient flow.

5.14 SYSTEM PIPING - THROUGH BOILER

In new or retrofit applications in which primary/secondary arrangement is not used, the Esteem boiler

allows this flexibility due to a lower boiler pressure drop, see the charts in Figure B-1 and B-2 in

Appendix B.
Figure 5-7 illustrates a multiple zone valve system with a single system/boiler circulator. A by-pass

loop with a pressure differential valve must be installed on the system piping.
Figure 5-8 illustrates a single zone utilizing the boiler circulator as the system circulator.

5.15 SYSTEM PIPING - RADIANT HEATING

The heat exchanger design of the Esteem 399 Low NOx boiler allows operation in a condensing

mode. This feature requires no return water temperature regulation in radiant heating

applications.
The design and construction of the Esteem heat exchanger allows the installation of the boiler

on systems with non-oxygen barrier tubing.

CAUTION

DO NOT install a water storage tank along with the unit in
systems with non-oxygen barrier tubing. Failure to comply
could result in premature failure of the storage tank.

A high temperature limit

should be installed to ensure that the primary supply temperature does

not exceed the maximum allowable temperature for the radiant tubing.
The addition of the high temperature limit is important if the Esteem boiler is connected to a
domestic hot water system, which requires a high primary supply water temperature.

Size the system piping and circulator to provide the flow needed for the radiant system.

NOTES

To ensure an adequate flow rate through the Esteem 399 Low

NOx boiler, the boiler supply and return piping size must be a

minimum of 1-1/2” (inches).

The addition of the high temperature limit is important if the

Esteem boiler is connected to a domestic hot water system,

which requires a high primary supply water temperature.