GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.3.11 Warm Weather Shutdown (Default: Off)

Figure 18-15: WARM WEATHER SHUTDOWN Menu

Warm Weather Shutdown allows the installer to enter an optional out-door temperature at which

to disable the central heating function. The Esteem will continue to respond to a domestic hot

water call or a 0-10V Modulation Signal when the outdoor temperature exceeds the Warm

Weather Shutdown Temperature setting. Press the LEFT or RIGHT buttons to adjust the Warm

Weather Shutdown Temperature then press the OK button to store the setting. The Warm

Weather Shutdown icon

is displayed on the home screen when the outdoor temperature

reaches the Warm Weather Shutdown Temperature.

========================================================================

18.3.12 Pump Constant Circulation (Default: Disabled)

Figure 18-16: PUMP CONSTANT CIRCULATION Menu

Pump Constant Circulation allows the central heating circulators to be constantly enabled even

without a central heating call. A domestic hot water call will cause the circulators to be disabled

during the domestic callas long as DHW Priority is enabled. Press the UP or DOWN buttons to

select Enabled or Disabled then press the OK button to store the setting.

Enabled: The central heating circulators will be enabled for constant circulation without a

central heating call.

Disabled: The central heating circulators will only be enabled during a central heating call.

Table 18-1: Circulator Operation with Pump Circulation = Enabled

CH2 Pump/System Pump Auxiliary Boiler Pump DHW Pump CH (1) Pump

ON

ON

OFF

ON

Page 126 of 188