18.9.12 DHW Proportional Gain (Default: 7)

DHW Proportional Gain allows the cascade response to be adjusted for a domestic hot water

call. DHW Proportional Gain has the greatest influence when the system temperature is far

away from the setpoint. Press the LEFT or RIGHT buttons to adjust the DHW Proportional Gain

then press the OK button to store the setting.

Figure 18-63: DHW Proportional Gain Menu

Increase DHW Proportional Gain:

The Cascade System will reach setpoint faster, but over shooting the setpoint may occur.

To reach the setpoint faster, increase the DHW Proportional Gain value by 2. Perform

Cascade Auto-detection and initiate a domestic hot water call. Observe the cascade

response and make further adjustments if necessary.

Decrease DHW Proportional Gain:

The Cascade System will take longer to reach the setpoint, but setpoint overshooting is

minimized.

If the setpoint is reached too quickly, decrease the DHW Proportional Gain value by 2.

Perform Cascade Auto-detection and initiate a domestic hot water call. Observe the

cascade response and make further adjustments if necessary.

NOTE

Only make adjustments to this setting after consulting AERCO

Technical Support. Improper adjustment of DHW Proportional Gain

could lead to temperature fluctuations and erratic cascade

operation.

========================================================================