beautypg.com

8 domestic hot water ez setup, 1 select dhw demand (default: switch), 2 boiler dhw setpoint (default: 186 f [86 c]) – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 74: 2 boiler dhw setpoint (default: 186°f [86°c])

background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 10

OMM-0089_0A

Installation, Operation & Maintenance Manual EZ-SET Controller

10.8 DOMESTIC HOT WATER EZ SETUP

Navigation: Home Screen > Main Menu > EZ Setup > DHW EZ Setup

Domestic Hot Water EZ Setup allows the installer to quickly customize the domestic hot water

settings for the application.

10.8.1 Select DHW Demand (Default: Switch)

Select DHW Demand prompts the installer to select the type of device which will generate a

DHW call. Press the UP or DOWN buttons to select the DHW Demand type then press the OK

button to store the setting. The Select DHW Demand options are:

Switch: A domestic hot water call from an aquastat or dry contact switch will enable the

Esteem with a fixed setpoint for a domestic hot water call.

Sensor: This option requires the use of Indirect Water Heater Sensor

69107

. The

Esteem will monitor the DHW storage temperature and generate a domestic hot water

call when the temperature drops below the DHW Storage Setpoint by 6ºF [3ºC].

Figure 10-10: Select DHW Demand Menu

10.8.2 Boiler DHW Setpoint (Default: 186°F [86°C])

Boiler DHW Setpoint prompts the installer to enter the fixed boiler setpoint temperature during a

Domestic hot water call when the Switch option is chosen in Select DHW Demand. Press the

LEFT or RIGHT buttons to adjust the Boiler DHW Setpoint then press the OK button to store the

setting.

Figure 10-11: Boiler DHW Setpoint Menu

Page 74 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288