17.17 FLAME SIGNAL INSPECTION

The flame signal can be read from the Boiler Information screen. It should be a min. 1μ Α−DC.

Check the igniter for fouling or damaged insulation if a low flame signal is observed.

Check ground wiring and continuity as a cause for low flame signal. Replace igniter if

conditions are satisfactory.

17.18 COMBUSTION LEVELS INSPECTION

Refer to Section

12.3.4 of this manual for measuring combustion levels and burner adjustments.

17.19 FLUE GAS TEMPERATURE CHECK

Checking the Flue Gas Temperature

1. Manually place the boiler into high fire. See Section 12.3.4 for procedure.
2. Navigate to the Boiler Information Menu to observe the flue gas temperature. See Section

10-12 for procedure.

3. If the flue gas temperature is more than 54°F [30°C] above the supply water temperature,

shut the boiler down and follow the heat exchanger cleaning procedure described in the next

section.