CHAPTER 17: MAINTENANCE PROCEDURES

WARNING!

The Esteem boiler should be inspected and serviced annually,

preferably at the start of the heating season, by a qualified service

technician. In addition, the maintenance and care of the unit as

out-lined in chapter 16, and further explained in this chapter, should

be performed to assure maximum efficiency and reliability of the

unit. Failure to service and maintain the Esteem boiler and the

system components could result in equipment failure, causing

possible severe personal injury, death or substantial property

damage.

NOTE

The following information provides detailed instruction for

completing the maintenance items outlined in the maintenance

schedule in Chapter 12. In addition to this maintenance, the

Esteem boiler should be serviced at the beginning of the heating

season by a qualified service technician.

17.1 REPORTED PROBLEMS

Any problems reported by the owner should be checked, verified and corrected before

proceeding with any maintenance procedures.

17.2 SURROUNDING AREA INSPECTION

Verify that the area surrounding the Esteem boiler is free of combustible / flammable materials or

flammable vapors or liquids. Remove immediately if found.
Verify that combustion air inlet area is free of any contaminates. Refer to the materials listed

section 3.2 of Chapter 3 of this manual. If any of these products are in the area from which the

unit takes its combustion air, they must be removed immediately or the combustion air intake

must be relocated to another area.

17.3 BURNER AREA INSPECTION

Remove the boiler front jacket panel and Venturi inlet elbow. Vacuum any dirt or debris from the

burner/blower components. Re-install Venturi inlet elbow and front jacket panel when completed.

WARNING!

Do not use solvents to clean any of the burner components. The

components could be damaged, resulting in unreliable or unsafe

operation.