beautypg.com

AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 26

background image

GF-135

Esteem 399 Low NOx Boiler

Chapter 2

OMM-0089_0A

Installation, Operation & Maintenance Manual

Combustion Air/Venting

3.8

REMOVAL OF AN EXISTING BOILER FROM A COMMON VENT SYSTEM

WARNING!

Do not install the esteem unit into a common vent with other gas

or oil appliances. This may cause flue gas spillage or appliance

malfunction, resulting in possible severe personal injury, death or

substantial property damage.

NOTE

When an existing boiler is removed from a common venting

system, the common venting system is likely to be too large for

proper venting of the remaining appliances.

At the time of removal of an existing boiler, the following steps shall be followed with each

appliance remaining connected to the common venting system placed in operation, while the

other appliances remaining connected to the common venting system are not in operation.

Seal any unused openings in the common venting system.

Visually inspect the venting system for proper size and horizontal pitch and determine

there is no blockage or restriction, leakage, corrosion and other deficiencies which could

cause an unsafe condition.

Insofar as is practical, close all building doors and windows and all doors between the

space in which the appliances remaining connected to the common venting system are

located and other spaces of the building. Turn on clothes dryers and any appliance not

connected to the common venting system. Turn on any exhaust fans, such as range

hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a

summer exhaust fan. Close fireplace dampers.

Operate the appliance being inspected. Follow the lighting instructions. Adjust thermostat

so appliance will operate continuously.

Test for spillage at the draft hood relief opening after 5 minutes of main burner operation.

Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.

After it has been determined that each appliance remaining connected to the common

venting system properly vents when tested as outlined above, return doors, windows,

exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous

condition of use.

Any improper operation of the common venting system should be corrected so the

installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or

CAN/CGA B149, Installation codes. When re-sizing any portion of the common venting

system, the common venting system should be re-sized to approach the appropriate

tables in Part II of the National Fuel Gas Code ANSI Z223.1/NFPA 54 and/or CAN/CGA

B149, Installation codes.

Page 26 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288