GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.3.17 CH Call Blocking (Default: 1 Minute)

Figure 18-21: CH CALL BLOCKING Menu

CH Call Blocking sets the minimum time between burner firings for central heating calls. At the

completion of a burner firing, the CH Call Blocking time will begin. The burner will not fire again

until after the CH Call Blocking time has elapsed. The CH Call Blocking time only prevents the

burner from firing, the central heating circulators will respond to a central heating call. This

blocking time has no affect on domestic hot water calls. The CH Call Blocking feature prevents

short cycling of the burner and extends the life of the burner components. Press the LEFT or

RIGHT buttons to adjust the CH Call Blocking time then press the OK button to store the setting.
========================================================================

18.3.18 System Pump (Default: CH1/CH2)

Figure 18-22: SYSTEM PUMP Menu

System Pump allows the system pump operation to be adjusted for the application. Press the

UP or DOWN buttons to select the desired System Pump operation then press the OK button to

store the setting. The System Pump options are:

Page 130 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14