Installation, Operation & Maintenance Manual Maint. Procedures

17.4 SYSTEM PIPING INSPECTION

Inspect all piping (water and gas) on the boiler system for leaks and verify that the piping is leak

free and properly supported. Inspect the fittings and components on the unit and verify they are

leak free.

WARNING!

Eliminate all boiler water system leaks. Continual fresh make-up

water will reduce the heat exchanger life causing boiler failure.

Leaking water may also cause severe property damage to the

surrounding area. Inspect the gas supply piping using the

procedure outlined in section 12.3.3.

17.5 CLEAN CONDENSATE DRAIN ASSEMBLY

Cleaning the Condensate Drain Assembly

1. Loosen the retaining nut from the condensate drain assembly and disconnect the assembly

from the boiler.

2. Empty any water from the trap and drain assembly. Flush with fresh water as necessary to

clean.

3. Check the drain piping from the condensate drain assembly to the drain. Flush to clean as

necessary.

4. Reassemble the condensate drain assembly onto the boiler by tightening the retaining nut

with rubber seal onto the boiler. Hand tighten only.

5. Remove the fill plug on the condensate drain assembly and fill with water. See Figure 6-1.
6. Replace the fill plug on drain assembly.

17.6 VENTILATION AIR OPENINGS INSPECTION

Verify that all ventilation openings to the mechanical room or building are open and

unobstructed. Check the operation and wiring of any automatic ventilation dampers.

Check and verify the vent discharge and the combustion air intake are free of debris and

obstructions.

17.7 VENT AND COMBUSTION AIR PIPING INSPECTION

Visually inspect the venting system and combustion air piping for blockage, deterioration

or leakage. Repair any deficiencies.

Verify that the combustion air inlet piping is connected, sealed and properly supported.

WARNING!

Failure to inspect the vent system and combustion air inlet piping

and to have any conditions repaired can result in severe personal

injury or death.

Page 110 of 188