AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 82

background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 10

OMM-0089_0A

Installation, Operation & Maintenance Manual EZ-SET Controller

Table 10-4: Manual Reset Hard Lockout Descriptions

Code

Lockout Message

Description

E1

Failed Ignition

The burner failed to light after 5 ignition attempts.

E2

False Flame

A flame is being detected prior to ignition.

E3

High Boiler Temperature

Boiler temperature exceeds 212°F [100ºF]

E5

Blower Speed

Blower is not at correct speed or speed signal is not

being received by control module.

E8

Flame Circuit Error

Flame circuit test failed.

E9

Gas Valve Circuit Error

Gas valve circuit test failed.

E13

Reset Limit Reached

Resets are limited to 5 every 15 minutes.

E15

Sensor Drift

Supply or return sensor reading has drifted.

E16

Supply Sensor Stuck

Supply sensor reading is not changing.

E17

Return Sensor Stuck

Return sensor reading is not changing.

E18

Sensor Failure

Supply or return sensor reading changed very rapidly.

E21

Internal Control Fault

A / D conversion error.

E30

Supply Sensor Shorted

A short circuit has been detected in the boiler supply

temperature sensor circuit.

E31

Supply Sensor Open

An open circuit has been detected in the boiler supply

temperature sensor circuit.

E43

Return Sensor Shorted

A short circuit has been detected in the boiler return

temperature sensor circuit.

E44

Return Sensor Open

An open circuit has been detected in the boiler return

temperature sensor circuit.

E80

Return > Supply

Return temperature is higher than supply temperature.

E87

External Limit Open

An external manual reset limit has opened.