beautypg.com

Chapter 11: start-up preparation, 1 check boiler system water chemistry, 1 water ph level 6.0 to 8.0 – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 85: 2 water hardness less than 7 grains, 3 chlorinated water, 4 flush boiler to remove sediment, Chapter 11, Start-up preparation

background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 11

OMM-0089_0A

Installation, Operation & Maintenance Manual Start-Up Preparation

CHAPTER 11: START-UP PREPARATION

NOTE

Requirements below must be met for warranty coverage of Esteem

heat exchangers. A thorough cleaning of any existing system,

using approved heating system cleaning agents is required prior to

installation of the Esteem boiler. System should be treated with an

approved inhibitor after filling for long term protection.

11.1 CHECK BOILER SYSTEM WATER CHEMISTRY

WARNING!

Do not use petroleum-based cleaning or sealing compounds in the

boiler system. Damage to seals and gaskets in the sys-tem

components could occur, resulting insubstantial property damage.

NOTE

System water including additives must be practically non-toxic,

having a toxicity rating or Class of 1, as listed in Clinical Toxicology

of Commercial Products.

11.1.1 Water pH Level 6.0 to 8.0

Maintain the boiler water pH between 6.0 and 8.0. Check using litmus paper or contact a water

treatment company for a chemical analysis.
If the pH does not meet this requirement, do not operate the Esteem or leave the unit filled until

the condition is corrected.

11.1.2 Water Hardness Less Than 7 Grains

For areas with unusually hard water (hardness above 7 grains) consult a water treatment

company.

11.1.3 Chlorinated Water

Do not use the Esteem 399 to heat a swimming pool or spa directly.
Maintain the chlorine level of the water at levels considered safe for drinking.

11.1.4 Flush Boiler to Remove Sediment

The installer must flush the boiler system to remove any sediment to allow proper operation of

the Esteem 399.
Flush the systems until the water runs clean and is free of sediment.
For zoned systems, each zone should be flushed through a purge valve. Purge valves and

isolation valves should be installed on each zone to allow proper flushing of the system.


Page 85 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288