Table 10-2: Outdoor Reset Preset Selections

Preset

Minimum Setpoint

Maximum Setpoint

Low Mass Radiant

80ºF [27ºC]

140ºF [60ºC]

High Mass Radiant

80ºF [27ºC]

120ºF [49ºC]

Cast Iron Baseboard

100ºF [38ºC]

170ºF [77ºC]

Finned Tube Baseboard

120ºF [49ºC]

180ºF [82ºC]

Radiators

120ºF [49ºC]

170ºF [77ºC]

Fan Coil

140ºF [60ºC]

180ºF [82ºC]

10.7.6 Set Warm Weather Shutdown Temperature (Default: OFF)

Warm Weather Shutdown prompts the installer to enter an optional outdoor temperature at which

to disable the central heating function. The Esteem will continue to respond to a domestic hot

water call or a 0-10VModulation Signal when the outdoor temperature exceeds the Warm

Weather Shutdown Temperature setting. Press the LEFT or RIGHT buttons to adjust the Warm

Weather Shutdown Temperature then press the OK button to store the setting. The Warm

Weather Shutdown icon ( ) is displayed on the home screen when the outdoor temperature

reaches the Warm Weather Shutdown Temperature.