2 ch1 setpoint (default: 180 f [82 c]), 3 ch2 setpoint (default: 140 f [60 c]), 2 ch1 setpoint (default: 180°f [82°c]) – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 72: 3 ch2 setpoint (default: 140°f [60°c])

background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 10

OMM-0089_0A

Installation, Operation & Maintenance Manual EZ-SET Controller

10.7.2 CH1 Setpoint (Default: 180°F [82°C])

CH1 Setpoint prompts the installer to enter the fixed setpoint for a CH1 heating call when a

Setpoint option is chosen in Select CH Demand. Press the LEFT or RIGHT buttons to adjust the

CH1 Setpoint then press the OK button to store the setting.

Figure 10-7: Select CH1 Setpoint Menu (Same as CH2 Setpoint Menu)

10.7.3 CH2 Setpoint (Default: 140°F [60°C])

CH2 Setpoint prompts the installer to enter the fixed setpoint for a CH2 heating call when a

Setpoint option is chosen in Select CH Demand. Press the LEFT or RIGHT buttons to adjust the

CH2 Setpoint then press the OK button to store the setting.

10.7.4 Select CH1 Reset Curve (Default: Finned Tube Baseboard)

Select CH1 Reset Curve prompts the installer to select an outdoor reset curve for a CH1 heating

call when an Outdoor Reset option is chosen in Select CH Demand. Outdoor reset curve

presets are available to cover most applications. The outdoor reset curve can also be adjusted

to any desired settings in the Installer Menu. Press the UP or DOWN buttons to select the

outdoor reset curve appropriate for the type of heating system then press the OK button to store

the setting.

10.7.5 Select CH2 Reset Curve (Default: Low Mass Radiant)

Select CH2 Reset Curve prompts the installer to select an outdoor reset curve for a CH2 heating

call when an Outdoor Reset option is chosen in Select CH Demand. Outdoor reset curve

presets are available to cover most applications. The outdoor reset curve can also be adjusted

to any desired settings in the Installer Menu. Press the UP or DOWN buttons to select the

outdoor reset curve appropriate for the type of heating system then press the OK button to store

the setting.

Figure 10-8: Select CH1 Reset Curve Menu (Same as CH2 Reset Curve Menu)

Page 72 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288