beautypg.com

2 natural gas supply pressure requirements, 3 propane gas, 1 pipe sizing – propane gas – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 47: 3 propane gas 7.3.1 pipe sizing – propane gas

background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 7

OMM-0089_0A

Installation, Operation & Maintenance Manual Gas Piping

7.2.2 Natural Gas Supply Pressure Requirements

Pressure required at the gas valve inlet supply pressure port:

o

Maximum 13” W.C. at flow or no flow conditions to the burner.

o

Minimum 5” W.C. during flow conditions to the burner. Must be verified during start up

and with all other gas appliances operating within the building.

Install 100% lockup gas pressure regulator in the gas supply line if inlet pressure can

exceed 13” W.C. at any time. Adjust the lockup pressure regulator for 13”w.c maximum.

WARNING!

Do not adjust or attempt to measure gas valve outlet pressure. The

gas valve is factory-set for the correct outlet pressure. This setting

is suitable for natural gas and propane and requires no field

adjustment. Attempts by the installer to adjust or measure the gas

valve outlet pressure could result in damage to the valve, causing

potential severe personal injury, death or substantial property

damage.

NOTE

The natural gas orifice for the Esteem 399 Low NOx boiler is 0.339” (8.6

mm).

7.3 PROPANE GAS

7.3.1 Pipe Sizing – Propane Gas

Contact the local propane gas supplier for recommended sizing of piping, tanks and 100%

lockup gas regulator.

WARNING!

The unit is shipped with a propane conversion kit, which is located

on the top of the unit in the instruction packet. This kit includes all

the necessary parts and instructions to perform the conversion

from natural gas to propane gas. If this conversion kit is missing,

please contact AERCO Technical Support before installing the

Esteem boiler to use propane gas.

WARNING!

Prior to start up, ensure the unit is set to fire propane.

Check the rating label for the type of fuel.

Check the gas valve for propane conversion label.

If there is a conflict or doubt on the burner set up, remove the gas

valve and check for the propane orifice (Figure 7-2). Failure to

ensure proper burner setup could result in severe personal injury,

death or substantial property damage.