GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.9.3 Stage Delay (Default: 60 Seconds)

Stage Delay sets the time delay before enabling or disabling a boiler in the Cascade System.

The Stage Delay begins once the Master boiler determines that a boiler must be enabled to

reach the setpoint or when the Master boiler deter-mines a boiler should be disabled because of

a decreasing load.

Figure 18-56: Stage Delay Menu

Press the LEFT or RIGHT buttons to adjust the Stage Delay then press the OK button to store

the setting. Adjusting the Stage Delay will have the following effects:
Increase Stage Delay:

Reaching the setpoint could take longer due to a longer delay between enabling boilers.

Overshooting the setpoint could occur due to boilers staying on longer before being

disabled.

Decrease Stage Delay:

Overshooting the setpoint could occur due to boilers being enabled quicker.

Boilers will be disabled quicker, possibly increasing boiler cycling and decreasing runtimes.

========================================================================

18.9.4 Minimum firing Rate (Default: 30%)

Minimum Firing Rate is the minimum firing rate of a single boiler in the Cascade System. The

Master boiler uses this setting to determine when boilers can be enabled and disabled. Setting

the Minimum Firing Rate below the recommended minimum will result in boilers being enabled

too quickly which may cause sharp increases in temperature from the Cascade System. Setting

the Minimum Firing Rate above the recommended minimum will delay the enabling of boilers

which may lower the system efficiency.

Figure 18-57: Minimum Firing Rate Menu

Press the LEFT or RIGHT buttons to adjust the Minimum Firing Rate then press the OK button to

store the setting.

NOTE

The recommended minimum firing

rate for the Esteem 399 is 30%