18.4.12 Antilegionella Function (Default: DISABLED)

Figure 18-38: ANTILEGIONELLA FUNCTION Menu

The Antilegionella Function ensures that an Indirect Water Heater is heated at least once per

week to prevent the growth of Legionella bacteria. Press the UP or DOWN buttons to select

Enabled or Disabled then press the OK button to store the setting.

Enabled: When the Switch option is chosen in DHW Demand, a domestic hot water call is

generated for 15 minutes once per week to heat the Indirect Water Heater. When the

Sensor option is chosen in DHW Demand, a domestic hot water call is generated until the

DHW storage temperature reaches 140°F [60°C] once per week. When the Sensor option

is chosen in DHW Demand, the weekly timer is reset whenever the DHW storage

temperature reaches 140°F [60°C] to prevent unnecessary firings. This function will be

active even if DHW Operation has been set to Disabled.

Disabled: The boiler will only fire in DHW mode when a domestic hot water call is received.

WARNING!

The Antilegionella function should only be enabled when an indirect

water heater is installed. Enabling the Antilegionella function

without an indirect water heater will result in the boiler firing once

per week in DHW mode, which could cause a manual reset hard

lockout resulting in substantial property damage.

NOTE

The Antilegionella Function is most effective when the Sensor

option is chosen in DHW demand. The use of an Indirect Water

Heater Sensor ensures that the domestic hot water is heated to

140°f [60°c] at least once per week.