GF-135 Esteem 399 Low NOx Boiler

Chapter 10

OMM-0089_0A

Installation, Operation & Maintenance Manual EZ-SET Controller

Table 10-5: Automatic Reset Soft Lockout Descriptions

Code

Lockout Message

Description

E7

High Flue Temperature

Flue temperature exceeds high limit.

E12

Internal Control Fault

EEPROM misconfiguration.

E25

Internal Control Fault

CRC check error.

E32

DHW Sensor Shorted

A short circuit has been detected in the DHW temperature

sensor circuit.

E33

DHW Sensor Open

An open circuit has been detected in the DHW

temperature sensor circuit.

E34

Low Voltage

Line voltage has fallen below an acceptable operating

level.

E37

Low Water

Water level has fallen below an acceptable operating level.

E45

Flue Sensor Shorted

A short circuit has been detected in the boiler flue

temperature sensor circuit.

E46

Flue Sensor Open

An open circuit has been detected in the boiler flue

temperature sensor circuit.

E76

External Limit Open

An external automatic reset boiler limit has opened.

E81

Sensor Drift

Supply and return temperatures are not equal.

E89

Incorrect Setting

A parameter setting is outside the settings range.

E90

Firmware Mismatch

Control module and display firmware versions are

incompatible.

E91

System Sensor Shorted

A short circuit has been detected in the system

temperature sensor circuit.

E92

System Sensor Open

An open circuit has been detected in the system

temperature sensor circuit.

E93

Outdoor Sensor Shorted

A short circuit has been detected in the outdoor

temperature sensor circuit.

E94

Internal Display Fault

Display memory error.

E95

Supply Sensor Error

Supply sensor reading is invalid.

E96

Outdoor Sensor Open

An open circuit has been detected in the outdoor

temperature sensor circuit.

E97

Cascade Mismatch

Cascade configuration has changed.

E98

Cascade Bus Error

Communication with other boilers has been lost.

E99

Controller Bus Error

Communication between boiler display and control module

has been lost.