GF-135 Esteem 399 Low NOx Boiler

Chapter 7

OMM-0089_0A

Installation, Operation & Maintenance Manual Gas Piping

7.3.2 Propane Gas Supply Pressure Requirements

1. Adjust the propane supply regulator provided by the gas supplier for 13” W.C. maximum

pressure.

2. Pressure required at the gas valve inlet supply pressure port:

Maximum 13” W.C. at flow or no flow conditions to the burner.

Minimum 5” W.C. during flow conditions to the burner. Must be verified during start

up and with all other gas appliances operating within the building.

WARNING!

Do not

adjust or attempt to measure gas valve outlet pressure.

The gas valve is factory-set for the correct outlet pressure. This

setting is suitable for natural gas and propane and requires no field

adjustment. Attempts by the installer to adjust or measure the gas

valve outlet pressure could result in damage to the valve, causing

potential severe personal injury, death or substantial property

damage.

WARNING!

Prior to start up, ensure the unit is set to fire propane. Check the

rating label for the type of fuel. Check the gas valve for propane

conversion label. If there is a conflict or doubt on the burner set up,

remove the gas valve and check for the propane orifice. See Figure

7-2. Failure to ensure proper burner setup could result in severe

personal injury, death or substantial property damage.

NOTE

The propane orifice required for the Esteem 399 Low NOx boiler is

0.264” (6.7 mm).



Page 48 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14