GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.4.6 DHW Storage Adder (Default: 46°F [25°C])

Figure 18-32: DHW STORAGE ADDER Menu

DHW Storage Adder is used to compute the boiler setpoint when the Sensor option is chosen in

DHW Demand. The boiler setpoint will be DHW Storage Setpoint + DHW Storage Adder for a

domestic hot water call. Press the LEFT or RIGHT buttons to adjust the DHW Storage Adder

then press the OK button to store the setting.
========================================================================

18.4.7 DHW Post Pump Time (Default: 1 Minute)

Figure 18-33: DHW POST PUMP TIME Menu

DHW Post Pump Time sets how long the domestic hot water circulator will continue to operate at

the completion of a domestic hot water call. Any call during the DHW Post Pump Time will be

ignored until the post pump has completed. The DHW Post Pump feature allows the heat

remaining in the boiler at the completion of a call to be sent to the Indirect Water Heater, which

will improve the overall efficiency of the system. Press the LEFT or RIGHT buttons to adjust the

DHW Post Pump Time then press the OK button to store the setting.