beautypg.com

3 circulator wiring – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 56

background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 9

OMM-0089_0A

Installation, Operation & Maintenance Manual External Wiring

9.3 CIRCULATOR WIRING

To wire the circulator, perform the following.

Wiring the Circulator

1. Reference Table 9-1 to determine the appropriate circulator connections required. The

circulator connections used will depend on the systems piping layout.

Table 9-1: Circular Operation Default Settings

Call

CH (1) Pump

DHW Pump

Auxiliary

Boiler Pump

System

Pump

CH 1 or CH 2 Call

ON

OFF (Note 1)

ON

ON

DHW Call

OFF (Note 1)

ON

ON

OFF (Note 1)

NOTE 1

Domestic Hot Water Priority can be disabled in the Installer Menu

which allows the CH (1) and DHW circulators to operate at the

same time. Consult Chapter 10, Basic Esteem Controls, for more

information.

NOTES

The system circulator can also been enabled during a DHW Call

in the Installer Menu. Consult Section 10, Basic Esteem

Controls, for more information.

Each circulator is individually fused with a 2.5A fuse located in

the terminal strip. The total combined amp draw of the CH (1),

DHW, and Auxiliary Boiler Circulators must not exceed 3 amps at

any time for the Esteem boiler. Use an isolation relay to lower the

total combined amp draw if exceeding these limits.

2. Connect the CH circulator to the line voltage terminal strip on the wiring panel below the

Esteem control module, as shown in Figure 8-3. The CH circulator is enabled during a CH 1

or CH 2 call. This circulator is used to supply heat to the central/space heating loop.

3. Connect the DHW circulator to the line voltage terminal strip on the wiring panel below the

Esteem control module, as shown in Figure 8-3. The DHW circulator is enabled during a

DHW call. This circulator is used to supply heat to an indirect hot water heater.

4. Connect the Auxiliary Boiler circulator to the line voltage terminal strip on the wiring panel

below the Esteem control module, as shown in Figure 8-3. The auxiliary boiler circulator is

enabled during a CH or a DHW call. This circulator is typically used in retrofit applications

where the CH and DHW systems are connected to a common boiler supply.

5. Connect the System circulator to the line voltage terminal strip on the wiring panel below the

Esteem control module, as shown in Figure 8-3 The system circulator is enabled during a

CH1 or CH2 call with the factory default settings. This circulator is typically used to circulate

water in the secondary CH loop when zoning with zone valves.


Page 56 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288