GF-135

Esteem 399 Low NOx Boiler

Chapter 2

OMM-0089_0A

Installation, Operation & Maintenance Manual

Combustion Air/Venting

WARNING!

The space must be provided with ventilation combustion air

openings properly sized for all make-up air requirements (exhaust

fans, clothes dryers, etc.), which includes the total input of all

appliances located in the same space as the Esteem unit(s) using
indirect

vented air. Esteem units installed with direct vent air

inputs are excluded from such consideration because they receive

combustion air directly from the outside, and so additional free

area for the openings is not required. Failure to provide properly
sized openings could result in severe personal injury, death
or property damage.

3.4 VENTILATION AND COMBUSTION AIR REQUIREMENTS -
CATEGORY IV

A Category IV appliance uses uncontaminated indoor or outdoor air (surrounding the appliance)

for combustion.

Piping uncontaminated combustion air directly from the outdoors to the appliance is
recommended. This reduces the risks associated with indoor contaminates, flammable vapors
and tight housing construction. This practice also promotes higher system efficiency.

In installations where the Esteem boiler shares the space with air movers (exhaust fan, clothes

dryers, fireplaces, etc.) and other combustion equipment (gas or oil), the space must be

provided with adequate air openings to provide ventilation and combustion air to all the

equipment. Sizing of the ventilation / combustion air openings must comply with the National

Fuel Gas Code NFPA 54, ANSI Z223.1 for installations in the U.S. or CSA B149.1 and B149.2

for installations in Canada, as referenced in this chapter of the manual and titled Methods of

Supplying Combustion Air to a Space.

3.5 METHODS OF SUPPLYING COMBUSTION AIR TO A CONFINED
SPACE - CATEGORY IV

NOTE

The methods listed in this section for accessing Indoor

Combustion Air assume that the infiltration rate is adequate and

not less than .40 ACH. For infiltration rates less than .40 ACH,

reference the NFPA 54 National Fuel Gas Code for additional

guidance.