GF-135

Esteem 399 Low NOx Boiler

Chapter 2

OMM-0089_0A

Installation, Operation & Maintenance Manual

Installation

CHAPTER 2:

INSTALLATION

2.1 CODE COMPLIANCE

This product must be installed in accordance to the following:

All applicable local, state, national and provincial codes, ordinances, regulations and

laws.

For installations in Massachusetts, code requires the boiler to be installed by a licensed

plumber or gas fitter, and if antifreeze is utilized, the installation of a reduced pressure

backflow preventer device is required in the boiler’s cold water fill or make up water

supply line.

For installation in Massachusetts all direct vented appliances must comply with the

guidelines as outlined in section 1.3 of Chapter 1.

The National Fuel Gas Code NFPA54/ ANSI Z 223.1—Latest edition.

National Electric Code ANSI/NFPA 70.

For installations in Canada -“Installation Code for Gas Burning Equipment” CGA/B149.1

or B149.2 Canadian Electrical Code Part 1 CSA C22.1.

Standards for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME

CSD-1, when required.

NOTE

The Esteem 399 Low NOx boiler gas manifold and gas controls

meet the safe lighting and other performance requirements as

specified in ANSI Z21.13 latest edition.

2.2 DETERMINING PRODUCT LOCATION

Before locating the Esteem 399 Low NOx check for convenient locations to:

Heating system piping

Venting

Gas supply piping

Electrical service

Ensure the boiler location allows the combustion air/vent piping to be routed directly through the

building and terminate properly outside with a minimum amount of length and bends.
Ensure the area chosen for the installation of the Esteem 399 is free of any combustible

materials, gasoline and other flammable liquids.
The Esteem boiler is certified for indoor conditioned space only.

WARNING!

Failure to remove or maintain the area free of combustible

materials, gasoline and other flammable liquids or vapors can

result in severe personal injury, death or substantial property

damage.

Ensure the Esteem 399 and its controls are protected from dripping or spraying water during

normal operation or service.