beautypg.com

Chapter 3: combustion air and venting, 1 combustion air contamination, 2 potential contaminating products – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 19: Chapter 3, Combustion air and venting

background image

GF-135

Esteem 399 Low NOx Boiler

Chapter 2

OMM-0089_0A

Installation, Operation & Maintenance Manual

Combustion Air/Venting

CHAPTER 3: COMBUSTION AIR AND VENTING

3.1 COMBUSTION AIR CONTAMINATION

WARNING!

If the Esteem boiler combustion air inlet is located in any area

likely to cause or contain contamination, or if products, which

would contaminate the air cannot be removed, the combustion air

must be re-piped and terminated to another location.

Contaminated combustion air will damage the unit and its burner

system, resulting in possible severe personal injury, death or

substantial property damage.

WARNING!

Do not operate the Esteem boiler if its combustion air inlet is

located near a laundry room or pool facility. These areas will

always contain hazardous contaminants.

Pool and laundry products and common household and hobby products often contain fluorine or

chlorine compounds. When these chemicals pass through the burner and vent system, they can

form strong acids. These acids can create corrosion of the heat exchanger, burner components

and vent system, causing serious damage and presenting a possible threat of flue gas spillage

or water leakage into the surrounding area.
Please read the information listed below. If contaminating chemicals are located near the area

of the combustion air inlet, the installer should pipe the combustion air inlet to an outside area

free of these chemicals per Chapter 5 of this installation manual.

3.2 POTENTIAL CONTAMINATING PRODUCTS

Spray cans containing chloro/fluorocarbons

Permanent Wave Solutions

Chlorinated wax

Chlorine—based swimming pool chemicals / cleaners

Calcium Chloride for melting ice

Sodium Chloride for water softening

Refrigerant leaks

Paint or varnish removers

Hydrochloric acid / muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry

rooms

Adhesives used to fasten building products and other similar products


Page 19 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14