beautypg.com

8 boiler system inspection, 9 expansion tank inspection, 10 boiler relief valve inspection – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 111

background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 17

OMM-0089_0A

Installation, Operation & Maintenance Manual Maint. Procedures

17.8 BOILER SYSTEM INSPECTION

Verify all system components are correctly installed and operating properly.

Check the cold fill pressure for the system, typical cold water fill pressure is 12 psig.

Verify the system pressure, as the unit operates at high temperature, to ensure the

pressure does not exceed 25 psig. Excessive pressure reading indicates expansion tank

sizing is incorrect or system performance problems.

Inspect air vent and air separators in the sys-tem. Remove the caps on automatic air

vents and briefly depress the valve stem to flush vent. Replace the cap when completed.

Ensure vents do not leak, replace any leaking vents.

Verify boiler water pH level is between 6.0 and 8.0.

Check and verify inhibitor /antifreeze concentration within the boiler water meets

inhibitor/antifreeze manufacturer’s specifications.

If necessary contact a boiler water treatment company for a chemical analysis.

17.9 EXPANSION TANK INSPECTION

Refer to Chapter 5: Boiler Piping for recommended location of the expansion tank and air

eliminators.

Closed -Type Tank:

Ensure tank is partially filled with water leaving an air gap as a cushion. Refer to the

manufacturer’s instruction for proper fill level.

Ensure the tank is fitted with a device that reduces gravity circulation of air-saturated tank

water back into the system. This device prevents air from bubbling up through the water

as it returns from the system.

Ensure no automatic air vents are used in the system. This will allow air to escape from

the system instead of returning to the tank.

Diaphragm Tank:

Ensure the system contains a minimum of one automatic air vent. Recommended

location of the air vent should be atop an air eliminator.

Remove the tank from the system and check the charge pressure. For residential

applications the charge pressure is typically 12 psig. If tank does not hold a charge

pressure, then the membrane is damaged and the tank should be replaced.

17.10 BOILER RELIEF VALVE INSPECTION

Inspect the relief valve and lift the lever to verify flow at least annually or as recommended on the

warning tag of the valve.

WARNING!

Before manually operating the pressure relief valve, ensure the

discharge piping is directed to a suitable place of disposal to avoid

a potential scald hazard. The discharge piping must be full size

without restriction and installed to permit complete drainage of both

the valve and line.

Page 111 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288