TROUBLESHOOTING/DIAGNOSTICS
FlexPak 3000
49’1340 e
7-4
7.7.2.1
Review Log
The Review Log selection displays the contents of the alarm log. Entries are listed from most
recent (higher numbered alarms) to the oldest (lower numbered alarms).
Review Log
➤
04 LOW MINIMUM SPEED
03 LINE VOLTAGE LOW
02 MOTOR BRUSH WEAR LOW
01 LINE VOLTAGE LOW
!!
!!
Fault
Alarm
Interlock OK
Drive Ready
Running
Current Limit
Torque Limit
ALARM
KEYPAD MANUAL FORWARD
Pressing ENTER will display details and possible causes of that specific alarm log entry.
A00051: LOW MINIMUM SPEED
138 days 16 hours 23 mins 52 secs
The MINIMUM SPEED value is less than 10%
of the MAXIMUM SPEED value. Verify that
these parameter values are correct for your
application.
!!
!!
Fault
Alarm
Interlock OK
Drive Ready
Running
Current Limit
Torque Limit
ALARM
KEYPAD MANUAL FORWARD
#
Indicates that more information is available. To view this information, press the down arrow
key. The remaining text for this specific alarm will be displayed when scrolling takes place.
Press the CANCEL key to exit this display.
7.7.2.2
Reset Alarm Indicator
Pressing ENTER with the cursor at Reset Alarms extinguishes the Alarm indicator and displays
the following message on the OIM display:
ATTENTION!
DRIVE ALARMS HAVE BEEN RESET.
Press CANCEL to continue.
Press CANCEL to continue.
NOTE: Alarms can also be reset by pressing the STOP/RESET key when the drive is stopped
and Control Source Select is set to KEYPAD.
7.7.2.3
Clear Alarm Log and Reset Alarms
Pressing ENTER with the cursor at Clear Alarm and Reset Alarms extinguishes the Alarm
indicator, resets drive alarms and displays the following message on the OIM display:
ATTENTION!
DRIVE ALARMS HAVE BEEN RESET.
ALARM LOG HAS BEEN CLEARED.
Press CANCEL to continue.