3 drive input/output specifications – Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual
Page 13
![background image](/manuals/581587/13/background.png)
INTRODUCTION TO THE DRIVE
49’1340 e
FlexPak 3000
2-5
2.3
Drive Input/Output Specifications
The following sections describe drive inputs and outputs. Refer to section 3.8 for terminal strip
connections and wiring diagrams.
2.3.1
Logic Inputs:
CAUTION:
Connecting an external power source to any of the +24 volt connections (terminals 1, 7, 11, and 14)
on the regulator board terminal strip will damage the drive. DO NOT connect the external power
source to the +24 volt connections on the regulator board terminal strip. Failure to observe this
precaution could result in damage to, or destruction of, the equipment.
The logic input circuits can be powered either from the internal +24 V DC power supply or from
an external +24 V DC power source. The internal +24 V DC power supply is available at the
regulator board terminal strip (see Figure 3-8). If an external power source is used, only its
COMMON must be connected to 24V COM on the regulator board (terminal 15). 24V COM is
internally not grounded, but may be externally grounded if required by the users control wiring.
Electrical Specifications:
Input Voltage ....................................................................................................... +24 V DC
Turn On Voltage .......................................................................................................... 8 V
Turn Off Current .................................................................................................... 0.5 mA
Common ............................................................ All input circuits have the same common.
2.3.2
Logic Outputs:
The logic output circuits are normally open (when de-energized) relay contacts. When
energized (contacts closed), the three circuits indicate the following drive conditions:
Running 27 to 28,
Alarm
29 to 30,
No Fault
31 to 32
Electrical Specifications:
Operating Voltage ................................................................ 250 V AC maximum
30 V DC maximum
Switching Current ............................................................ 2 A maximum resistive
1 A maximum inductive
2.3.3
Analog Inputs:
The three customer analog inputs are
•
Manual Mode Reference
•
Automatic Mode Reference
•
D-C Tachometer Feedback.
These inputs are converted at 12 bits plus sign at their full range. The electrical specifications
for each of these is listed below.
Electrical Specifications:
Current loading ...................................................................................... . 2.5 mA maximum
Manual Mode Reference:
Jumper J19
Potentiometer 5 kohm minimum
POT
External Voltage Source: +/- 10 VDC (when used for Analog Trim Ref. )
0 - 10 VDC (when used for Manual Mode Speed Ref.)
EXT
Automatic Mode Reference:
Jumper J12
Jumper J10
Voltage Reference
+/- 10 V DC
VOLTS
VOLTS & PARK
Milliamp Reference
4-20 milliamps
MAMPS
4-20
& PARK
10-50 milliamps
MAMPS
10-50
& 4-20