Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual
Page 65
QUICK START
49’1340 e
FlexPak 3000
6-3
ATTENTION:
The incorrect setting of the Quick Start parameters can cause an overspeed condition.
These parameters must be set by a qualified person who understands the significance of setting.
Verify that the value of these parameters is set accurately per your application requirements.
Failure to observe this precaution could result in bodily injury.
ATTENTION:
The parameter for the current transformer turns ratio (Tp/Tn) CT TURNS RATIO (P.010) is factory set
depending on the power unit size. Do not adjust/change the value of this parameter from its factory
default value unless you are replacing the regulator board without downloading of the parameter set. In
that case refer to Appendix B for setting the ratio (Tp/Tn).
Failure to observe this precaution could result in damage to, or destruction of, the equipment.
Table 6.2 - Quick Start Parameter Modification Sequence
Step
No.
Parameter
Name
Code
No.
Default
Description
User
Setting
1
TOP SPEED
011
500 RPM
The highest running speed of the motor. It
scales the feedback device.
TOP SPEED
depends on several factors:
•
If there is no field weakening, the top speed
is typically the same as the nameplate base
speed.
•
If there is field weakening, the Top Speed
is the same as the field weakened speed.
Top speed is typically more than the base
speed when field weakening is applied.
ATTENTION: Before starting the drive, this
parameter must be set to base speed or, if
the Field Current Regulator kit is installed,
the field weakened speed. You are
responsible for assuring safe conditions for
operating personnel by setting this
parameter properly. Failure to observe this
precaution could result in bodily injury.
Do not allow the motor to exceed the
maximum safe speed of the motor or driven
equipment as determined by the equipment
manufacturer. Failure to observe this
precaution can result in bodily injury
2
MOTOR
RATED ARM
AMPS
008
8 AMPS
ATTENTION: The drive will not operate
properly if this parameter value is wrong.
This parameter must be less than the rated
armature amps on the motor nameplate.
Failure to observe this precaution could
result in damage to, or destruction of, the
equipment.
The rated armature current from the motor
nameplate.