ANALOG TACH ZERO ADJ (P.202)
Used to remove any hardware-introduced offset from the analog tachometer feedback signal.
Typically, it will be 0.
Parameter Range:
-200 to + 200
Default Setting:
0
Parameter Type:
Tuneable
OIM Menu Path(s):
Speed/Voltage Loop (SPD)-Speed /Voltage Loop (SPD) Feedback
WARNING
The incorrect setting of this parameter can cause an overspeed condition. This parameter must be set
by a qualified person who understands the significance of setting it. Set the value of this parameter
accurately per your application requirements. Failure to observe this precaution could result in bodily
injury.
ANLG AUTO GAIN ADJ (P.101)
Used to scale the analog auto reference signal after it has been conditioned by the drive hardware.
Typically, it will be 1.000.
Parameter Range:
0.750 to 1.250
Default Setting:
1.000
Parameter Type:
Tuneable
OIM Menu Path(s):
Drive Reference - Drive Reference Scaling
ANLG AUTO SIGNAL TYPE (P.100)
Selects the analog auto reference signal type.
Parameter Range:
0 - 10V
+/-10V
4 - 20mA 10 - 50mA
Default Setting:
0 - 10V
Parameter Type:
Configurable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure
Note: Jumpers J10 and J12 must be set for the type of auto reference selected.
ANLG AUTO ZERO ADJ (P.102)
Used to remove any hardware introduced offset from the analog auto reference signal.
Typically, it will be 0.
Parameter Range:
-200 to + 200
Default Setting:
0
Parameter Type:
Tuneable
OIM Menu Path(s):
Drive Reference - Drive Reference Scaling