Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual
Page 158

APPENDIX C
FlexPak 3000
49’1340 e
C-2
ANLG IN 1 (P.492)
Only available if the I/O Expansion kit is installed.
The value representing analog input 1 (terminals 50 and 51 on the I/O Expansion board) after gain and
zero have been applied. See ANLG IN 1 GAIN ADJ for block diagram.
OIM Menu Path(s):
Input/Output - Analog I/O
Refer also to Parameters:
ANLG IN 1 SIG TYPE (P.413),
ANLG IN 1 ZERO ADJ (P.414)
ANLG IN 1 GAIN ADJ (P.415)
ANLG IN 2 (P.493)
Only available if the I/O Expansion kit is installed.
The value representing analog input 2 (terminals 52 and 53 on the I/O Expansion board) after gain and
zero have been applied.
OIM Menu Path(s):
Input/Output - Analog I/O
Refer also to Parameters:
ANLG IN 2 GAIN ADJ (P.417),
ANLG IN 2 ZERO ADJ (P.416)
ARMATURE BRIDGE POL (P.394)
Indicates which bridge is currently active. OFF indicates the forward bridge; ON indicates the reverse
bridge.
OIM Menu Path(s):
Current Minor Loop (CML) - CML Test Points
ARMATURE DELTA (P.399)
Indicates the armature firing angle in microseconds.
OIM Menu Path(s):
Current Minor Loop (CML) - CML Test Points
Current Minor Loop (CML) - SCR Diagnostics
Armature Phase Fire Test
ARMATURE VOLTAGE (P.289)
Armature voltage value after all hardware and software scaling.
OIM Menu Path(s):
SPD - SPD Test Points,
SPD - SPD Feedback
Current Minor Loop (CML) -SCR Diagnostics - Armature Phase Fire Test
CML ERROR (P.398)
The CML error signal (i.e., the difference between CML REFERENCE and CML FEEDBACK).
OIM Menu Path(s):
Current Minor Loop (CML) - CML Test Points
CML FEEDBACK (P.397)
The CML feedback signal prior to the summing junction.
OIM Menu Path(s):
Current Minor Loop (CML) - SCR Diagnostics - Armature Phase Fire Test
Current Minor Loop (CML) - CML Feedback Scaling
Current Minor Loop (CML) - CML Test Points