Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual
Page 69
![background image](/manuals/581587/69/background.png)
QUICK START
49’1340 e
FlexPak 3000
6-7
Step
No.
Parameter
Name
Code
No.
Default
Description
User
Setting
18
MOTOR HOT
FLD AMPS
510
0.01amps
This parameter only needs to be set if a field
current regulator is installed. Motor nameplate
value of the rated hot field amps. This input is
the basis of field current scaling.
If the factory defaults are restored, or if a valid
value has not yet been entered for this
parameter, the DC field voltage is fixed at
150V on a 230VAC line, or at 300V on a
460VAC line.
ATTENTION You must configure this to the
motor nameplate value. The incorrect
configuration of this parameter can cause a
motor overvoltage condition. Configure
MOTOR HOT FLD AMPS
to the motor’s
nameplate value. Failure to observe this
precaution can result in bodily injury and
damage to the equipment
19
Jumper
Informat.
Display
J11
J14
792
793
N/A
ATTENTION: The drive will not operate at
the correct speed if these jumpers are not
set to the correct positions. Set these
jumpers to the positions as displayed in the
"Quick Start" procedure for the drive to
operate at the correct speed.
Failure to observe this precaution could
result in damage to, or destruction of, the
equipment.
J11
J14
J18 395
The OIM displays the correct jumper positions
for J11, J14 and J18. Record these positions
in the space provided. Verify that the hardware
for these jumpers is positioned the same
before continuing with Quick Start.
J18
20
Self
Tune?
NO
YES
N/A N/A
N/A
NO - Returns the display to the Main Menu.
Perform a memory save to store values to
retentive memory.
YES - Proceeds with the Self-Tuning
procedure. Refer to the Self-Tuning section of
this instruction manual before proceeding with
self-tuning.
Not Re-
quired
N/A = Not Applicable.