Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual
Page 130
APPENDIX B
FlexPak 3000
49’1340 e
B-26
MAXIMUM SPEED (P.004)
The maximum speed of the drive that can be supported by the application or process. MAXIMUM
SPEED can be less than or equal to TOP SPEED.
If raising this value causes MINIMUM SPEED to become less than 10% of MAXIMUM SPEED, an alarm
is generated.
Parameter Range:
1 to TOP SPEED (RPM or user-defined units)
Default Setting:
500 RPM
Parameter Type:
Tuneable
OIM Menu Path(s):
Drive Reference - Drive Reference Limits Quick Start
Refer also to Parameters:
TOP SPEED (P.011)
WARNING
The incorrect setting of this parameter can cause an overspeed condition. This parameter must be set
by a qualified person who understands the significance of setting it. Set the value of this parameter
accurately per your application requirements. Failure to observe this precaution could result in bodily
injury.
WARNING
When performing this adjustment, do not allow the motor to exceed the maximum safe speed of the
driven equipment as determined by the equipment manufacturer. Failure to observe this precaution
could result in bodily injury.
METER OUT 1 GAIN ADJ (P.400)
Scales the Meter 1 Output Signal at the regulator board terminal strip.
Parameter Range:
0.100 to 1.900
Default Setting:
1.000
Parameter Type:
Tuneable
OIM Menu Path(s):
Input/Output - Meter Outputs
NOTE: Testpoint METER OUT FULL SCALE must source METER OUT 1 SELECT for an accurate
adjustment. See Appendix D, figure D.8, for further details.