Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual
Page 204

APPENDIX G
FlexPak 3000
49’1340 e
G-4
Table G.1 - User Quick Reference Table for Input Parameters (continued)
Par.
Parameter
Parameter Selection /
Pg Initial Factory
User Data
No.
Adjustment Range
B-
Setting
Date
Setting
Current Regulator Set-up
300
CML FEEDBACK GAIN ADJ
0.800 - 2.000
9
1.000
301
CML PI PROP GAIN
0.000 - 4.000
9
0.250
302
CML PI LEAD FREQ
10 - 500 rad/s
9
100 rad/s
303
CML REF RATE LIMIT
1 - 1000 msec
10
40 msec
306
NOMINAL AC LINE FREQ
48 - 62 Hz
36
50 Hz
307
NOMINAL AC LINE VOLTS
200 - 575 VAC or
300 - 850 VAC (types 575/690 V)
36
400 VAC
308
PLL MAXIMUM ERROR
2 - 1000
µ
sec
42
2
µ
sec
309
PHASE FIRE TEST DELTA
0 - 180 degrees
41
0 degrees
310
PHASE FIRE TST BRIDGE
•
OFF
•
ON
42
OFF
311
CML REF LIMIT SELECT
•
1 = SPD LOOP PI LIMITS
•
2 = REGISTER
10
1
312
INV FAULT AVOID SEL
•
1 = DISABLED
•
2 = FAULT IMMEDIATELY
•
3 = DELAY BEFORE FAULT
21
DISABLED
Meter Outputs Set-up
400
METER OUT 1 GAIN ADJ
0.100 - 1.900
26
1.000
401
METER OUT 2 GAIN ADJ
0.100 - 1.900
28
1.000
402
METER OUT 1 ZERO ADJ
-200 - +200
27
0
403
METER OUT 2 ZERO ADJ
-200 - +200
28
0
404
METER OUT 1 SELECT
•
CML FEEDBACK
•
CML REFERENCE
•
CML ERROR
•
SPD LOOP FEEDBACK
•
SPD LOOP REFERENCE
•
SPD LOOP ERROR
•
SPD LOOP OUTPUT
•
SPEED RAMP OUTPUT
•
SPEED RAMP INPUT TP
•
SPD SOURCE SELECT OUT
•
TRIM OUTPUT
•
ARMATURE VOLTAGE
•
ANALOG TACH FEEDBACK
•
PULSE TACH FEEDBACK
•
ZERO
•
FULL SCALE
•
POWER OUTPUT
•
OCL REFERENCE
•
OCL RAMP OUTPUT
•
OCL FEEDBACK
•
OCL OUTPUT
•
FIELD REFERENCE
•
FIELD FEEDBACK
•
NETW IN REG 1
•
NETW IN REG 2
•
NETW IN REG 3
27
CML
FEEDBACK
405
METER OUT 2 SELECT
same as above for P.404
28
SPD LOOP
FEEDBACK