DIG OUT 1 CONTACT TYP (P.410)
Only available if the I/O Expansion Kit is installed. Selects whether digital output 1 (terminals 66 and 67
on I/O Expansion board) is normally open or normally closed.
Parameter Range:
NORMAL OPEN
NORMAL CLOSED
Default Setting:
NORMAL OPEN
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Digital I/O
Refer also to Parameters:
DIG OUT 1 SELECT (P.409)
If NORMAL OPEN is selected, digital output 1 is open when the signal is off and closed when it is on.
If NORMAL CLOSED is selected, digital output 1 is closed when the signal is off and open when on.
DANGER
On a power cycle or reset, the contact is held at normally open until the drive software is initialized.
Make sure that this condition does not result in a dangerous situation for your application. Failure to
observe this precaution can result in severe bodily injury or loss of life.
DIG OUT 1 SELECT (P.409)
Only available if the I/O Expansion Kit is installed. Selects the signal that drives digital output 1
(terminals 66 and 67 on the I/O Expansion board).
DANGER
This output is intended for use as an indication. If it is used as a control source, a dangerous condition
can result. Failure to observe this precaution can result in severe bodily injury or loss of life.
Parameter Range:
LEVEL DETECT 1 OUTPUT,
LEVEL DETECT 2 OUTPUT
IN CURRENT LIMIT,
DRIVE READY
NETW COMM STATUS,
NETW IN REG 1 (bit 0)
NETW IN REG 2 (bit 0),
NETW IN REG 3 (bit 0)
Default Setting:
LEVEL DETECT 1 OUTPUT
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Digital I/O
Refer also to Parameters:
LEVEL DETECT 1 OUTPUT (P.648),
LEVEL DETECT 2 OUTPUT (P.649)
NETW COMM STATUS (P.908), NETW IN REG 1 (P.905)
NETW IN REG 2 (P.906),
NETW IN REG 3 (P.907)
DIG OUT 2 CONTACT TYP (P.412)
Only available if the I/O Expansion Kit is installed. Selects whether digital output 2 (terminals 68 and 69
on the I/O Expansion board) is normally open or normally closed.
Parameter Range:
NORMAL OPEN,
NORMAL CLOSED
Default Setting:
NORMAL OPEN
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Digital I/O
Refer also to Parameters:
DIG OUT 2 SELECT (P.411)
If NORMAL OPEN is selected, digital output 2 is open when the signal is off and closed when it is on.
If NORMAL CLOSED is selected, digital output 2 is closed when the signal is off and open when it is on.
DANGER
On a power cycle or reset, the contact is held at normally open until the drive software is initialized.
Make sure that this condition does not result in a dangerous situation for your application. Failure to
observe this precaution can result in severe bodily injury or loss of life.