Table E.1 - Fault Codes (Continued)
CODE
DISPLAY
DESCRIPTION
F00006 BLOWER MOTOR
STARTER OPEN
This fault is not applicable on European versions FlexPak 3000.
F00007 OPEN ARMATURE The motor armature circuit is open.
Possible causes:
•
Motor armature winding not connected or open circuit.
•
Blown inverting fault (DC) fuse.
•
Excessive armature voltage at motor speeds <5% of TOP SPEED,
Refer to Appendix B, TACH LOSS SCR ANGLE (P608).
F00008
MOTOR
THERMOSTAT TRIP
Motor thermostat indicates high temperature. If a motor thermostat is
not used, customer terminal board pins 13 and 14 must be jumpered to
inhibit this fault.
Possible causes:
•
Damaged or disconnected motor thermostat wiring.
•
Inadequate ventilation.
•
Blower motor failure.
•
Incorrect blower rotation.
•
Blocked ventilation slots.
•
Clogged filters.
•
Excessive armature current.
•
One or more thyristors not operating.
F00009
CONTROLLER
THERMOSTAT TRIP
Controller thermostat indicates high temperature.
Possible causes:
•
Inadequate heat sink ventilation.
•
Inadequate cabinet ventilation.
•
Heat sink fan failure.
•
Damaged or disconnected controller thermostat wiring.
F00010
AC LINE
SYNCHRONIZATION
FAULT
Three-phase AC line synchronization circuit failure.
Possible causes:
•
Blown AC line fuse(s).
•
AC line frequency not within required range of 48-62Hz.
•
Excessive AC line noise or distortion.
•
Unstable AC line frequency.
•
Disconnected, loosely connected or damaged J6 ribbon cable.
F00011
OIM
COMMUNICATIONS
TIMEOUT
The regulator board was unable to communicate with the Operator
Interface Module (OIM). (Refer to section 7.7.5 which discusses the
regulator status LEDs that can pinpoint whether or not the OIM is
communicating)
Possible causes:
•
Disconnected, loosely connected, or damaged OIM cable.
•
OIM failure.
•
Regulator board failure.
F00012
ARMATURE OVER
VOLTAGE
Armature voltage exceeded 130% of
MOTOR RATED ARM VOLTS (P.009)
.
Possible causes:
•
MOTOR RATED ARM VOLTS
not set properly.
•
Improper voltage loop tuning.
•
ENHANCED FLD VOLT ADJ
(P.500)
set too high (Enhanced Field
Supply kit only).