Selects stopping mode of the drive in response to a normal STOP command. An open permissive will
always cause a coast stop. If the drive is configured as a current regulator, only COAST/DB can be
selected.
Parameter Range:
RAMP,
COAST/DB,
CURRENT LIMIT
Default Setting:
RAMP
Parameter Type:
Tuneable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure
STOP SPEED THRESHOLD (P.113)
Sets the threshold speed below which the main contactor will automatically open after a ramp stop or
current limit stop is asserted. This value should be less than or equal to MINIMUM SPEED.
Parameter Range:
0 to MAXIMUM SPEED (RPM or user-defined units)
Default Setting:
0 (RPM or user-defined units)
Parameter Type:
Tuneable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure
TACH LEAD FLT DELAY (P.228)
The amount of time that parameter TACH LEAD FLT THRESH (P.227) must be exceeded before a
REVERSED TACH LEADS fault (F00014) is generated.
Parameter Range:
0 to 32767 msec
Default Setting:
10 000 msec
Parameter Type:
Tuneable
OIM Menu Path(s):
Additional Parameters
Refer also to Parameters:
TACH LEAD FLT THRESH (P.227)