APPENDIX B
FlexPak 3000
49’1340 e
B-12
DECELERATION TIME (P.002)
Selects the time it takes to decelerate from TOP SPEED to 0. Smaller changes in speed take
proportionately less time.
If TRIM MODE SELECT is set to PROPORTIONAL, this time value is modified by DRAW
PERCENTAGE OUT.
Parameter Range:
0.1 to 300.0 seconds
Default Setting:
5.0 seconds
Parameter Type:
Tuneable
OIM Menu Path(s):
Drive Reference - Drive Reference Ramp Quick Start
Refer also to Parameters:
DRAW PERCENTAGE OUT (P.196)
ANLG AUTO ZERO ADJ (P.102)
TOP SPEED (P.011)
TRIM MODE SELECT (P.110)
RAMP STOP DECEL TIME (P.018)
DEVICENET POLL MSG (P.913)
Selects which predefined set of data will be part of the DeviceNet poll connection command/response
messages. The amount of data transmitted in the CONTROL ONLY poll message type allows greater
network density and performance. The larger amount of data transmitted in the CONTROL+CONFIG
poll message type allows some degree of drive configuration but decreases the network scan rate.
Parameter Range:
CONTROL ONLY,
CONTROL+CONFIG
Default Setting:
CONTROL ONLY
Parameter Type:
Configurable
If the AutoMax Network Communication board is being used, this parameter has no effect.
DIG IN 0 SELECT (P.428)
Determines which function is controlled by DIG IN 0 (Regulator board terminal 12).
Parameter Range:
1 = BRUSH WEAR,
2 = JOG SPEED SELECT
3 = OCL ENABLE
Default Setting:
1
Parameter Type:
Configurable
OIM Menu Path(s):
Additional Parameters
Refer also to Parameters:
DIG IN 0 (P.490)
The functions can be:
•
BRUSH WEAR
: To use this option, a brush wear indicator device must be installed. If the input is
OFF
,
the
MOTOR BRUSH WEAR LOW
alarm is generated.
•
JOG SPEED SELECT
: The input determines whether
JOG SPEED
1 (P.012) or
JOG SPEED
2 (P.017) will
be used when the drive is jogging.
•
OCL ENABLE
: Enables the outer control loop if
CONTROL SOURCE SELECT
is not set to
NETWORK
and if
the I/O Expansion kit is not installed. If an I/O Expansion kit is installed, the outer control loop enable
signal is digital input 5.
OCL ENABLE
* BRUSH WEAR
JOG SPEED SELECT
Network OCL Enable
Regulator board
Digital Input (term. 12)
NETWORK
TERMBLK
*KEYPAD
CONTROL
SOURCE
SELECT
OFF
Not Running
Running
Drive
Status
(OCL ENABLE)
OCL enable
P.849
P.000
I/O Expansion Kit
I/O Expansion
Digital Inputs (terminal 64)
(DIG IN 5)
P.499
(DIG IN 0)
P.490
disable
DIG IN 0 SELECT
P.428
SERIAL
Installed
Not Installed