Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual
Page 129
APPENDIX B
49’1340 e
FlexPak 3000
B-25
LEVEL DETECT 2 SELECT (P.605)
Selects the signal that drives level detector 2. See LEVEL DETECT 1 SELECT for discussion and block
diagram.
Parameter Range:
SPD SOURCE SELECT OUT
SPEED RAMP INPUT TP
SPEED RAMP OUTPUT
SPD LOOP FEEDBACK
CML FEEDBACK
Default Setting:
SPEED RAMP INPUT TP
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Level Detectors
Refer also to Parameters:
LEVEL DETECT 1 SELECT (P.602), LEVEL DETECT 2 DELAY (P.607),
LEVEL DETECT 2 OUTPUT (P.649), LEVEL DETECT 2 THRESH (P.606)
LEVEL DETECT 2 THRESH (P.606)
The threshold for level detector 2. See LEVEL DETECT 1 SELECT for discussion and block diagram.
Parameter Range:
0.1 to 100.0% or MAXIMUM CURRENT %*
Default Setting:
10.0%
Parameter Type:
Tuneable
OIM Menu Path(s):
Input/Output - Level Detectors
Refer also to Parameters:
LEVEL DETECT 1 SELECT (P.602), LEVEL DETECT 2 DELAY (P.607),
LEVEL DETECT 2 OUTPUT (P.649), LEVEL DETECT 2 SELECT (P.605),
MAXIMUM CURRENT (P.007)
*The parameter range for the level detector is automatically rescaled for speed or current based on the
input selected by LEVEL DETECT 2 SELECT. If CML FEEDBACK is selected for LEVEL DETECT 2
SELECT, the parameter range is 0.1 to MAXIMUM CURRENT. For any other LEVEL DETECT 2
SELECT settings, the parameter range is 0.1 to 100.0%.
MANUAL REF SELECT (P.106)
Sets the reference for the speed/voltage loop when the drive is in manual mode and CONTROL
SOURCE SELECT is set to TERMBLK. If the I/O Expansion kit is not installed, this parameter is fixed to
ANALOG. This parameter is not accessible over the network.
When set to ANALOG, the analog MANUAL reference input (terminals 16, 17 and 18 on the regulator
board) is the reference.
When set to MOP, MOP OUTPUT parameter is the reference.
Parameter Range:
ANALOG
MOP
Default Setting:
ANALOG
Parameter Type:
Configurable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure
Refer also to Parameters:
CONTROL SOURCE SELECT (P.000)
MOP OUTPUT (P.191)
MAXIMUM CURRENT (P.007)
The highest amount of current (positive or negative) for a given application.
This input is used as the basis of armature current scaling.
MAXIMUM CURRENT is limited to 200% of MOTOR RATED ARM AMPS (P.008).
Parameter Range:
25 to 200% of P.008
Default Setting:
150%
Parameter Type:
Configurable
OIM Menu Path(s):
Current Minor Loop (CML) - CML Feedback Scaling
Refer also to Parameters:
MOTOR RATED ARM AMPS (P.008)