DRIVE SETUP AND ADJUSTMENT
FlexPak 3000
49’1340 e
4-2
4.5
Jumper Settings
The jumper settings for the FlexPak 3000 drive determine the regulator type, program
protection, field settings, references for automatic and manual modes, tachometer voltage
range, and armature feedback scaling.
•
Through the OIM, check the proper jumper settings for J11, J14, and J18 in the Correct
Scaling Jumper Positions menu under Drive Information. Write down these settings as
displayed and make sure the actual settings match.
•
Through the OIM, check the current settings for J15, J20, and J21 in the Drive Information
menu. If these settings are correct for your system, you do not need to change them.
DANGER
This equipment is at line voltage when A-C power is connected to the drive. Disconnect and lockout
incoming power to the drive before proceeding. After power is removed, verify with a voltmeter at
power terminals 1U, 1V and 1W that no voltage exists before touching any internal parts of the drive.
Failure to observe these precautions could result in severe bodily injury or loss of life.
CAUTION
Unless explicitly stated otherwise, power must be removed before changing any jumper connection.
Failure to observe this precaution could result in damage to, or destruction of, the equipment.
Jumpers are read only on power-up, so power must be cycled for a change to a jumper setting
to be recognized by the drive.
1. Remove power from the drive.
2. Remove the cover and the keypad
3. The jumpers are located on the regulator board. See Figure 4.1 for jumper locations
4. Change the jumper settings as described in the following paragraphs per the requirements
of your application. Record final settings in Table 4.1.
Table 4.1 - Jumper and Adjustment Settings
JUMPER/ADJUSTMENT
DEFAULT SETTING
FINAL SETTING
J10 (AUTO REF)
VOLTS
J11 (TACH V SCALE)
16
J12 (AUTO REF)
VOLTS
J14 (TACH V RANGE)
62
J15 (REGULATOR TYPE)
SPEED
J16 (OIM PROGRAM)
ENABLE
J18 (ARM I FB RB)
Position 4
J19 (MANUAL REF)
POT
J20 (FIELD LOSS DETECT)
DISABLE
J21 (FIELD SUPPLY)
NOT APPLICABLE
1)
J26 (TACH LOSS DETECT)
ENABLE
J27, J29 for future selection needs
J28 (FILTER SELECT) (red)
FLDFBK (do not change)
FLDFBK
J30 (POWER INTERFACE)
LOW
ANALOG TACH ZERO ADJ
0
ARM VOLTAGE ZERO ADJ
0
(1)
Only applicable when the optional Enhanced Field Supply kit is installed.