APPENDIX B
49’1340 e
FlexPak 3000
B-37
OCL FEEDBACK SELECT (P.804)
Selects the source for the outer control loop (OCL) feedback signal. The I/O Expansion kit must be
installed to use ANALOG IN 1, or ANALOG IN 2. An AutoMax network module must be installed and
CONTROL SOURCE SEL = NETWORK to access Selections 5 to 9.
Parameter Range:
NONE,
CML FEEDBACK,
ANALOG IN 1,
ANALOG IN 2
5 = SPEED LOOP OUTPUT,
6 = ANALOG AUTO REFERENCE
7 = NETW IN REG 1 (not available in SW-version 4.1)
8 = NETW IN REG 2 (not available in SW-version 4.1)
9 = NETW IN REG 3 (not available in SW-version 4.1)
Default Setting:
NONE
Parameter Type:
Enumerated input, configurable, retentive
OIM Menu Path(s):
Outer Control Loop (OCL) - OCL Configure
Refer also to Parameters:
CML FEEDBACK (P.397)
OCL LEADLAG LOW FREQ (P.806)
Lead/lag low break frequency of the outer control loop. Sets the lead break frequency if OCL LEADLAG
SELECT (P.807) is set to LEAD/LAG. Sets the lag break frequency if P.807 is set to LAG/LEAD.
Parameter Range:
0.01 to 34.90 RAD/S
Default Setting:
1.00 RAD/S
Parameter Type:
Tuneable
OIM Menu Path(s):
Outer Control Loop (OCL) - OCL Tuning
Refer also to Parameters:
OCL LEADLAG RATIO (P.807)
OCL LEADLAG SELECT (P.805)
The OCL lead/lag high break frequency is determined by the settings of this parameter and the OCL
LEADLAG RATIO. For example, if the low break frequency is 0.50 rad/s and the ratio is 10, the high
break frequency is 5.00 rad/s.
To Outer Control Loop
Block Diagram
OCL
FEEDBACK
SELECT
OCL
LEADLAG
SELECT
output of OCL
enable logic
OCL
LEADLAG
RATIO
OCL
LEADLAG
LOW FREQ
(O CL FEEDBACK)
CML FEEDBACK
ANALOG IN 1
ANALOG IN 2
From I/O Expansion
Inputs Block Diagram
(CML FEEDBACK)
8 sample average
{
*NONE
P.804
P.847
P.806
P.807
P.805
(A)
(B)
AUTO REF.
SPD LOOP OUTPUT
SPD LOOP OUTPUT 3)
ANALOG AUTO REFERENCE 3)
LEAD/LAG
* BYPASS
LAG/LEAD
INITV
L / L
WLD RST\ RATIO
OCL LEADLAG RATIO (P.807)
The ratio between the low break frequency and high break frequency of outer control loop lead/lag.
The settings of this parameter and the OCL LEADLAG LOW FREQ determine the high break frequency.
See OCL LEADLAG LOW FREQ for discussion and block diagram.
Parameter Range:
2 to 20
Default Setting:
10
Parameter Type:
Tuneable
OIM Menu Path(s):
Outer Control Loop (OCL) - OCL Tuning
Refer also to Parameters:
OCL LEADLAG LOW FREQ (P.806),
OCL LEADLAG SELECT (P.805)