3 installation and wiring, 1 general, 2 recommended ac line and dc armature fuses – Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual
Page 25: 3 install the drive
INSTALLATION AND WIRING
49’1340 e
FlexPak 3000
3-1
3.0
Install and Wire the Drive
DANGER
The user is responsible for conforming to all other applicable standards.
Wiring practices, grounding, disconnects, and overcurrent protection are of particular importance.
Size and install all wiring in conformance with the applicable standards.
Failure to observe this precaution could result in severe bodily injury or loss of life.
DANGER
This equipment must be connected to a power source for which it was designed. Compare available
power with the requirements listed on the nameplate to insure that voltage, frequency, phase, current
capacity and interrupting capacity are adequate.
Failure to observe this precaution could result in severe bodily injury or loss of life.
3.1
General
This Section outlines the procedures that are to be followed to properly install the FlexPak 3000
Drive.
3.2
Recommended AC Line and DC Armature Fuses
The user must select the correct fuse type (ultra fast, semiconductor protection) for drive AC
line and DC armature fuses from the table 8-7 in chapter 8. The armature fuse is only for four
quadrant drives (S-6R).
3.3
Install the Drive
Minimum clearances of 100 mm must be maintained when the drive is mounted within a
cabinet. This allows adequate ventilation around and through the drive.
Regardless of these placement guidelines, the user is responsible for ensuring that the Drive's
ambient temperature specification of 0 to 40
°
C is met and its relative humidity is kept within 5%
to 95% without condensation. Install the drive(s) in the cabinet.
Refer to Figures 3-1 to 3-6 for mounting dimensions.