Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual
Page 124
APPENDIX B
FlexPak 3000
49’1340 e
B-20
FREQ OUT FULL SCALE (P.427)
Only available if the I/O Expansion kit is installed.
The frequency generated when the signal driving the frequency output is at full scale.
For example, if FREQ OUT SELECT is set to CML FEEDBACK, the frequency specified by this
parameter is output when the armature current is at MAXIMUM CURRENT (MAXIMUM CURRENT is
used as the basis for current minor loop scaling).
Parameter Range:
2.0 to 250.0 kHz
Default Setting:
250.0 kHz
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Frequency I/O
Refer also to Parameters:
FREQ OUT SELECT (P.425),
MAXIMUM CURRENT (P.007)
FREQ OUT SELECT (P.425)
Only available if the I/O Expansion Kit is installed.
Selects the signal that drives the frequency output (terminals 42, 43, and 44 on the I/O Expansion
board). When the frequency output is at its maximum value, the selected signal is at its full scale value.
Parameter Range:
See table below for parameter options.
Default Setting:
ZERO
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Analog I/O
Refer also to Parameters:
MAXIMUM CURRENT (P.007),
MOTOR HOT FLD AMPS (P.510),
MOTOR RATED ARM AMPS (P.008),
MOTOR RATED ARM VOLTS (P.009),
TOP SPEED (P.011)
Signal Selected
Full Scale Value
CML FEEDBACK (P.397)
CML REFERENCE (P.396)
CML ERROR (P.398)
SPD LOOP OUTPUT (P.299)
±
MOTOR RATED ARM AMPS * MAXIMUM CURRENT
100
SPD LOOP FEEDBACK (P.296)
SPD LOOP REFERENCE (P.295)
SPD LOOP ERROR (P.297)
SPEED RAMP OUTPUT (P.199)
SPEED RAMP INPUT TP (P.198)
SPD SOURCE SELECT OUT (P.193)
TRIM OUTPUT (P.197)
ANALOG TACH FEEDBACK (P.291)
PULSE TACH FEEDBACK (P.292)
OCL OUTPUT (P.848)
±
TOP SPEED
ARMATURE VOLTAGE (P.289)
±
MOTOR RATED ARM VOLTS
POWER OUTPUT
±
MOTOR RATED ARM VOLTS * MOTOR RATED ARM AMPS * MAXIMUM CURRENT
100
FIELD REFERENCE (P.590)
FIELD FEEDBACK (P.589)
MOTOR HOT FLD AMPS
OCL REFERENCE (P.845)
±
4095
OCL RAMP OUTPUT (P.846)
OCL FEEDBACK (P.847)
NETW IN REG 1 (P.905)
NETW IN REG 2 (P.906)
NETW IN REG 3 (P.907)
FULL SCALE
ZERO
0