P.063 Option Port: Network Reference Source

This parameter
specifies where the
drive gets its speed
or torque reference
when the option port
is selected as the
control source
(P.000 = OP).

Parameter Range:

0 = Direct reference

1 to 8 = Broadcast

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters:

U.000 Torque Reference Source

Speed or torque control is configured by parameter U.000 (Torque Reference
Source) and by specifying TRQ/SPD in P.007 (Terminal Strip Digital Inputs
Configure). One of the selections in U.000 is the option port.

If P.063 = 0, the reference is from register 33 of the drive’s Drop_1 register map.

In V/Hz regulation, the value in register 33 represents speed in hertz scaled 0 to
4095 for 0 to Maximum Speed (P.004).

In vector regulation, if U.000 = 2, the value in register 33 represents torque scaled 0
to 4095 for 0 to 150% torque. If U.000

2, this value represents speed in RPM

scaled 0 to 4095 for 0 to Top Speed (U.017).

If P.063 = 1 to 8, the reference is from one of the eight network broadcast data
registers (network drop area 0, registers 32 to 39).

Refer to the

AutoMax Network Communications Module instruction manual

(J2-3001) for a description of network broadcast registers.