P.063 option port: network reference source – Rockwell Automation GV3000/SE AC Drive AutoMax Network Communication Board, M/N 2AX3000 User Manual
Page 54
Drive Configuration
3-7
P.063 Option Port: Network Reference Source
This parameter
specifies where the
drive gets its speed
or torque reference
when the option port
is selected as the
control source
(P.000 = OP).
Parameter Range:
0 = Direct reference
1 to 8 = Broadcast
Default Setting:
0
Parameter Type:
Configurable
Refer also to parameters:
U.000 Torque Reference Source
Speed or torque control is configured by parameter U.000 (Torque Reference
Source) and by specifying TRQ/SPD in P.007 (Terminal Strip Digital Inputs
Configure). One of the selections in U.000 is the option port.
If P.063 = 0, the reference is from register 33 of the drive’s Drop_1 register map.
In V/Hz regulation, the value in register 33 represents speed in hertz scaled 0 to
4095 for 0 to Maximum Speed (P.004).
In vector regulation, if U.000 = 2, the value in register 33 represents torque scaled 0
to 4095 for 0 to 150% torque. If U.000
≠
2, this value represents speed in RPM
scaled 0 to 4095 for 0 to Top Speed (U.017).
If P.063 = 1 to 8, the reference is from one of the eight network broadcast data
registers (network drop area 0, registers 32 to 39).
Refer to the
AutoMax Network Communications Module instruction manual
(J2-3001) for a description of network broadcast registers.