2.10 Connecting the GV3000/SE Drive to an AutoMax Network

See figure 2.21 for cabling and termination connections.

Refer to the Network Communications Module instruction manual (J2-3001) for a
detailed description of how to add a drop to the AutoMax network.

To connect the GV3000/SE drive to an AutoMax network:

Step 1. Stop any application tasks that are running.

Step 2. Use the 30-inch Network Drop Cable (M/N2NC3000) to connect to the

Communications Passive Tap (M/N57C380).

Step 3. If the drop is at the end of the coaxial cable system, it must be terminated.

Terminate by connecting a 75-ohm terminating load (M/N 45C71) to the
remaining

BNC

connector on the passive tap.

Step 4. Remove the lockout and tag. Apply power to the drive. SELF is displayed

while the drive performs power-up diagnostics. If there is an error during
diagnostics, it is logged. See the software manual for information on errors.

.

!

ATTENTION: AutoMax networks with more than 5 drops might produce
communication errors if 10-foot drop cables are used. Wherever possible,
30-inch drop cables or, if necessary, 5-foot drop cables should be used.
Failure to observe this precaution could result in damage to, or
destruction of, equipment.

Figure 2.21 – Connecting a GV3000/SE Drive to the AutoMax Network

RELIANCE
ELECTRIC

RELIANCE
ELECTRIC

RELIANCE
ELECTRIC

RELIANCE
ELECTRIC

RELIANCE
ELECTRIC

RELIANCE
ELECTRIC

RELIANCE
ELECTRIC

RELIANCE
ELECTRIC

75

Terminating Load

(M/N 45C71)

75

Terminating Load

(M/N 45C71)

Passive Tap

(M/N 57C380)

Drop Cable

(M/N 57C381)

Coaxial Cable

To GV3000/SE Drive

Passive Tap

(M/N 57C380)

BNC Connector

Drop Cable

(M/N 57C381)

Coaxial Cable

BNC Connector

Passive Tap

(M/N 57C380)

To GV3000/SE Drive