Installation

2-19

Step 4.5 Fasten the right side of the AutoMax Network option board to the keypad

bracket. Use the two metal M3 screws and lock washers for grounding.

Important: You must use the lock washers to properly ground the option board.

Improper grounding of the option board can result in erratic operation of
the drive.

Step 4.6 Fasten the left side of the AutoMax Network option board to the keypad

bracket using the two plastic rivets.

Step 5.

Reinstall the Keypad Bracket in the Drive

Step 5.1 Align the Regulator board ribbon cable connector with the connector to the

Base board. Carefully press the ribbon cable connector in until the retaining
clips lock into place.

Step 5.2 Place the keypad bracket back into position.

Figure 2.10 – Regulator Board’s Connections to Option Board, Keypad, and Base Board

Regulator Board

Top View

Ribbon Cable
Connecting
Regulator Board and
Base Board

Network

To Base Board

Front

Ribbon Cable
Connecting
Regulator Board and
Option Board

Metal Screw

Ribbon Cable
Connector to
Connect Base
Board

Ribbon Cable
Connector to
Connect Keypad

Plastic Rivet

Terminal Strip

Ribbon Cable
Connector to
Connect Option
Board

Back Side of

Insulator

Rear View of Regulator Board

Regulator Board