beautypg.com

Rockwell Automation GV3000/SE AC Drive AutoMax Network Communication Board, M/N 2AX3000 User Manual

Page 35

background image

2-26

AutoMax Network Communication Option Board for the GV3000/SE AC Drive

Step 2.

Verify That the DC Bus Capacitors are Discharged

Step 2.1 Use a voltmeter to verify that there is no voltage at the drive’s AC input

power terminals (1L1, 1L2, 1L3).

Step 2.2 Ensure that the DC bus capacitors are discharged. To check

DC bus potential:

a. Stand on a non-conductive surface and wear insulated gloves.

b. 50 to 100 HP @ 460 V only: Use a voltmeter to measure the DC bus

potential at the diode bridge. Refer to figure 2.14.

c. 100 to 150 HP @ 460 V only: Take care not to touch any conductive

traces. Use a voltmeter to measure the DC bus potential at the bottom of
the fuse holders on the Power Module Interface board on the back of the
Regulator panel. Refer to figure 2.15.

Step 3.

Remove the Keypad Bracket from the Drive

Step 3.1 Loosen the two screws from the top of the hinged panel (where the keypad

bracket is mounted). Tilt the mounting panel forward out of the chassis.

Step 3.2 Record connections to the Regulator board terminal strip if they must be

disconnected to remove the keypad bracket.

Step 3.3 Spread the retaining clips on the Regulator board’s 60-conductor ribbon

cable connector to disconnect it from the Power Module Interface board.
This ribbon cable runs from the top of the Regulator board through a slot in
the mounting panel to the Power board on the other side. Slip the ribbon
cable out of the slot to free it from the mounting panel.

Figure 2.14 – 50 to 100 HP GV3000/SE Drive Components and Locations

Keypad

Regulator
Board

Power Module
Interface Board

DC Bus

Measuring Points

+