C146, C147, C150 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 98: Communications group (continued)

98
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3
Programming and Parameters
Communications Group (continued)
C146 [EN Flt Cfg Ref]
32 bit parameter.
PowerFlex 525 only.
Sets the Reference data that is sent to the drive if any of the following is true:
–
[EN Comm Flt Actn] is set to 4 “Send Flt Cfg” and communications are disrupted.
–
[EN Idle Flt Actn] is set to 4 “Send Flt Cfg” and the scanner is put into Program or Test mode.
Values
Default:
0
Min/Max:
0/50000
Display:
1
32
PF 525
C147 [EN Flt Cfg DL 1]
C148 [EN Flt Cfg DL 2]
C149 [EN Flt Cfg DL 3]
C150 [EN Flt Cfg DL 4]
PowerFlex 525 only.
Sets the Ethernet Datalink Input data that is sent to the drive if any of the following is true:
–
[EN Comm Flt Actn] is set to 4 “Send Flt Cfg” and communications are disrupted.
–
[EN Idle Flt Actn] is set to 4 “Send Flt Cfg” and the scanner is put into Program or Test mode.
Values
Default:
0
Min/Max:
0/65535
Display:
1
PF 525
C153 [EN Data In 1]
C154 [EN Data In 2]
C155 [EN Data In 3]
C156 [EN Data In 4]
PowerFlex 525 only.
Datalink parameter number whose value is written from the embedded EtherNet/IP data table. This parameter cannot be changed when an I/O connection is established through the
drive’s embedded EtherNet/IP port.
Values
Default:
0
Min/Max:
0/800
Display:
1
PF 525
C157 [EN Data Out 1]
C158 [EN Data Out 2]
C159 [EN Data Out 3]
C160 [EN Data Out 4]
PowerFlex 525 only.
Datalink parameter number whose value is read from the embedded EtherNet/IP data table. This parameter cannot be changed when an I/O connection is established through the
drive’s embedded EtherNet/IP port.
Values
Default:
0
Min/Max:
0/800
Display:
1
PF 525